XM31-918-HP
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM31-918-HP
Firmware V1.04.0
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Float
Tamper Door closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 124.68 V
Current 2.86 A
Power 329 W
Frequency 60 Hz
Tap Status Buck tap
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 9,534 Wh
Output
Voltage 61.51 V
Power 201 W
Apparent Power 232.50 VA
Frequency 60.05 Hz
Percent Load 21.00 %
Output Setting 60 V
Output Regulation Coarse override
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 3.78 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Disable
Total Standby Events 111
Time Since Last Standby Event 86d 22h:15m
Time in Last Standby Event 0d 0h:10m
Total Time in Standby 1,433 min
Standby Events Since Reset 68
Time in Standby Since Reset 910 min
Time Since Reset 698 day(s)
Total Run Time 698 day(s)
Transformer Run Time 698 day(s)
Total Downtime 0d 20h:35m
Oil Cap Lifespan Consumed 24.0 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 13 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 
Copyright © 2017-2022 EnerSys. All Rights Reserved.